UPS sizing calculator
List the equipment you want to keep running. The calculator totals the load, allows headroom, converts watts to VA with the power factor and rounds up to a common UPS size.
UPS rating
2,000 VA
Recommended UPS rating, rounded up to a common size
- Total load
- 1,220 W
- With 25% headroom
- 1,525 W
- Exact requirement
- 1,906 VA
- Real power of that size
- 1,600 W
- Load on that size
- 76%
This load is above the largest common single-phase size here. A larger online UPS or a split load may suit. Send us the details.
Planning estimate. Backup time depends on the model and the batteries fitted, so it is matched to a model and not calculated here.
Choosing the type of UPS
Shutting down safely
A line-interactive UPS at the recommended rating normally gives enough time to save work and shut equipment down. Choose online if the mains is unstable or the load is sensitive.
| Feature | Line-interactive | Online | Online with external batteries |
|---|---|---|---|
| Best for | Desktop PCs, routers, PoE switches and small recorders where the mains is mostly stable. | Servers, recorders and equipment on poor or noisy mains, and sensitive loads. | Sites that need hours of backup, such as recorders that must run through long outages. |
| Power conditioning | Corrects voltage with automatic voltage regulation and passes mains through while it is within range. | Rebuilds the output continuously, so equipment is isolated from mains disturbances. | As online. |
| Switch to battery | A few milliseconds. | None. | None. |
| Backup time | Minutes, from the internal battery. | Minutes, from the internal battery. | Hours, set by the size of the external battery bank. |
| Points to weigh | Lower cost and quiet running. | Higher cost, fan noise and more heat. | The battery bank needs space and ventilation. Recharge time grows with the bank size. |
How the rating is worked out
The rating is a planning figure. It tells you the VA size to look for, and the datasheet of the model you choose has the final word on watts and backup time.
-
Total load
sum of (quantity x watts) for every row
-
Required watts
total load x (1 + headroom)
Headroom allows for growth and keeps the UPS away from its limit.
-
Required VA
required watts / power factor
Power factor links real power in watts to apparent power in VA. The default 0.8 is a planning value for line-interactive units. Many online units are rated at 0.9 or 1.0, and the watt rating on the datasheet is the limit that counts.
-
UPS rating
next common size at or above the required VA
Common sizes: 600, 1,000, 1,500, 2,000, 3,000, 5,000, 6,000, 10,000 VA.
-
Load on that size
total load / (rating x power factor)
| Rating | Watts at power factor 0.8 |
|---|---|
| 600 VA | 480 W |
| 1,000 VA | 800 W |
| 1,500 VA | 1,200 W |
| 2,000 VA | 1,600 W |
| 3,000 VA | 2,400 W |
| 5,000 VA | 4,000 W |
| 6,000 VA | 4,800 W |
| 10,000 VA | 8,000 W |
What the rating cannot know
- Backup time is specific to each model and its batteries. The calculator does not estimate it. Check the runtime chart on the datasheet at your load.
- Laser printers, motors and compressors draw a large surge at start-up. Size for the peak, or keep them off the UPS.
- The watt rating is the limit that counts, not the VA figure alone. Keep the load within it.